TS85 series transmitter can detect temperature and humidity data as well as CO2 or CO gas data. It adopts RS485 bus communication technology, standard ModBus RTU communication protocol, adjustable communication address and baud rate, rail installation, convenient and fast. It is a practical integrated sensor for online monitoring.
The product is divided into two models, TS85-A and TS85-B. The temperature and humidity sensor of TS85-A is an internal sensor, while the temperature and humidity sensor of TS85-B is an external sensor.
Feature introduction:
TS85-A detection type: CO+temperature and humidity
TS85-B detection type: CO2+temperature and humidity
2. Technical indicators
2.1 Power supply voltage range: DC9V~40V
2.2 Model: TS85-A/B
2.3 Measurement range: Temperature (external): -40 ℃~120 ℃; Temperature (built-in): -40 ℃~85 ℃; Humidity range: Humidity: 0~100% RH; CO2 range: 400~5000 PPM; CO range: 0~1000 PPM
2.4 Measurement accuracy: Temperature: ± 0.3 ℃, Resolution: 0.1 ℃; Humidity: ± 5.0% RH, resolution: 0.1% RH; CO2: ± 50ppm or ± 5% true value, whichever is greater; CO: ≤± 1ppm or ± 5% test value, whichever is greater
2.5 Response time: Temperature ≤ 1S, humidity ≤ 1S, CO2/CO ≤ 1S
2.6 Communication output interface: RS485
2.7 Baud rate: default 9600, can be set to 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
2.8 byte format: 8-bit data bits, 1 stop bit
2.9 Communication Protocol: Modbus RTU
2.10 Communication address can be set from 0 to 254
2.11 Installation method: rail installation
2.12 Shell material: ABS material
2.13 Shell size: 65mmX45mm